Battery lifespan: cycles vs depth of discharge

Performance4 min readUpdated: 2026-08

How many cycles a battery can handle depends heavily on the depth of discharge it is cycled at. Discharging less deeply each cycle multiplies total lifespan — sometimes at the cost of a larger bank.

DoD per cycleLiFePO4 cycles (indicative)Lead AGM/Gel cycles (indicative)
100%2,000–3,000150–250
80%3,000–6,000300–500
50%5,000–8,000600–1,000
20%8,000–15,000+1,500–2,500

Two aging mechanisms overlap: cyclic aging (wear from charge/discharge cycles) and calendar aging (chemical degradation over time, even without use). A lightly-cycled but 10-year-old battery can be more degraded than a heavily-cycled but recent one.

Temperature strongly accelerates calendar aging: each 10°C rise above 25°C can roughly halve a lead-acid battery's calendar lifespan.

To compare two options economically, calculate the cost per kWh actually delivered over the lifespan: (Capacity × DoD × Cycles) gives cumulative kWh, divided by purchase price.

Common mistakes

  • Comparing two batteries only on Ah capacity without accounting for recommended DoD
  • Ignoring calendar aging for a lightly-used system (holiday home)
  • Installing batteries in a poorly ventilated room where temperature regularly exceeds 35°C