Help CenterPV Calculations

How outage hours affect system sizing

Calculation3 min readUpdated: 2025-06

Daily outage hours directly determine the battery capacity needed in Backup mode. The longer the outages, the larger the battery must be.

Outages/dayBattery capacityTypical scenario
0hMinimal (15 min)Reliable grid — Europe
4hCritical load × 4hTypical urban Africa
8hCritical load × 8hPeri-urban areas
12hNight off-grid equivalentConnected rural areas
24hSame as Off-GridUnreliable grid
C_Ah = (P_critical × outage_hours) ÷ (V_sys × DoD)

P_critical = critical loads in Wh · outage_hours = outage duration / 24

In Hybrid mode, outages during solar hours don't impact the battery if PV produces enough. Only nighttime outages add to battery autonomy.

Common mistakes

  • Underestimating real outage hours by trusting the utility's official announcements
  • Sizing the Backup battery on total load instead of critical load only
  • Ignoring that outages during solar hours don't affect the battery in Hybrid mode