Sizing the inverter — kVA vs kW and power factor

Inverter4 min readUpdated: 2026-08

An inverter is always rated in kVA (apparent power), not kW (real power). For purely resistive loads (lighting, heating elements) the two are close, but for inductive loads (motors, AC units) the power factor (PF) widens the gap.

S [kVA] = P [kW] ÷ PF

Typical PF 0.8 for a residential mix with motors · PF = 1.0 for pure resistive loads

S_inverter ≥ P_continuous × 1.25

Minimum 25% safety margin above actual continuous power consumption

Continuous powerRecommended inverterTypical use
< 1 kW1.5–2 kVASmall household, lighting + electronics
1–2.5 kW3–3.5 kVAAverage household with a fridge
2.5–4 kW5 kVAHousehold with AC unit or pump
4–6 kW6–8 kVAVilla, small business

The kVA rating on the datasheet does not account for startup peaks. A 3 kVA inverter may handle 3 kW continuous but trip on an AC unit's 900 W startup (4.5 kW peak). Always check each appliance's surge factor.

SolarDim Pro computes the required kVA from continuous power AND the highest startup peak in the appliance table, not just the sum of rated powers.

Common mistakes

  • Adding up rated kW and buying an inverter of the same value in kVA
  • Ignoring power factor for a household with an AC unit, pump, or motor
  • Leaving no margin for future appliance additions